CE CB Approved 6ka MCB Circuit Breaker with Overload Protection Manufacturer

Product Details
Customization: Available
Breaking Capacity: Low Voltage Circuit Breakers
Operation: Electric Type
Still deciding? Get samples of US$ 1.8/Piece
Order Sample
Shipping & Policy
Shipping Cost: Contact the supplier about freight and estimated delivery time.
Payment Methods:
visa mastercard discover JCB diners club american express T/T
PIX SPEI OXXO PSE OZOW
  Support payments in USD
Secure payments: Every payment you make on Made-in-China.com is protected by the platform.
Refund policy: Claim a refund if your order doesn't ship, is missing, or arrives with product issues.
Manufacturer/Factory & Trading Company

360° Virtual Tour

Secured Trading Service
Diamond Member Since 2019

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
67
Year of Establishment
2000-07-14
  • CE CB Approved 6ka MCB Circuit Breaker with Overload Protection Manufacturer
  • CE CB Approved 6ka MCB Circuit Breaker with Overload Protection Manufacturer
  • CE CB Approved 6ka MCB Circuit Breaker with Overload Protection Manufacturer
  • CE CB Approved 6ka MCB Circuit Breaker with Overload Protection Manufacturer
  • CE CB Approved 6ka MCB Circuit Breaker with Overload Protection Manufacturer
  • CE CB Approved 6ka MCB Circuit Breaker with Overload Protection Manufacturer
Find Similar Products
  • Overview
  • Product Description
  • Detailed Photos
Overview

Basic Info.

Model NO.
SG65LE-63
Speed
Normal Type Circuit Breaker
Arc-extinguishing Medium
Air
Installation
Fixed
Structure
MCB
Poles Number
1p-4p
Function
Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection), RCCB
Certification
VDE, ISO9001-2000, CE, CB, CCC
Keyword
Circuit Breaker
Keyword2
MCB
Keyword3
Electric Circuit Breaker
Keyword4
Miniature Circuit Breaker
Keyword5
Circuit Breaker Factory Price
Transport Package
Seaway
Specification
6A to 125A
Trademark
SINGI OR OEM
Origin
China
HS Code
8536200000
Production Capacity
500000PCS/Year

Packaging & Delivery

Package Size
9.00cm * 3.00cm * 3.00cm
Package Gross Weight
0.100kg

Product Description

Product Description



Key Parameters:

  • CE/CB/ISO9001/CCC certificates;
  • Rated voltage:230/400VAC;
  • frequency50/60Hz;
  • Rated current:1,3,6,10,16,20,25,32,40,50,63A;
  • 1/2/3/4poles optional;
  • Mechniacal life:10,000times;
  • Flame-redardant:PA66 nylon material;
  • Protection degree:IP20;
  • With over load/short circuit protection;
  • Standard:IEC60898;
  • Enduring tem.55°C
  • Breaking Capacity:6KA;
  • Lighting/Motor protection optional

Application:

SG65LE RCBO is applied in the power system of AC 50Hz, single phase 230V, three phases 400V. When somebody gets and electric shock or the residual current exceeds the default value, the RCBO can cut off the powerautomatically to protect the personal safety and prevent the equipmentfrom the fault resulted from the residual current. It also can protect the circuit aqainst overload and short circuit or can be used for the unfrequent switch of the circuit under normal condition. And extra protection functions like over voltage, under voltage can be added according to customers' request.


It conforms to the standard IEC1009-1. GB16917.1.

 

Structure

SG65LE-63 series RCBO is composed of SG65-63 high breaking MCB and residual current release. This RCBO is current operating electronic RCBO, the main parts including zero sequence current transformer, electronic panel, current leakage release and the circuit breaker with protection functions of overload, short circuit.

 

Technical Parameters

 

Shell level rated current(A) voltage(V) Pole Rated current In(A) Rated short circuit breaking capacity Rated residual current breaking current(mA) Rated residual current no breaking current(mA) Trip time
Breaking capacity Ics(A) COSφ
63 230 1P+N

60,10,

16,20,

25,32,

40,50,

63

6000 0.75 10 5 ≤0.1S
230 2P 30 15
400 3P 50 25
400 3P+N 75 37.5
400 4P 100 50

 

Test current(A) Rated current(A) Requested time Result Start station Remark
1.13In all t>=1h Don't trip Cool  
1.45In All T<1h trip heat Current ascends the requested value stably in 5s
2.55In In<=32A 1s<t<60s trip Cool Auxiliary switch closed, power is on
2.55In In>32A 1s<t<120s trip Cool Auxiliary switch closed, power is on
3In(Bmode) All t>=0.1s Don't trip Cool Auxiliary switch closed, power is on
5In(Bmode) All T<0.1s trip Cool Auxiliary switch closed, power is on
5In(Cmode) All t>=0.1s Don't trip Cool Auxiliary switch closed, power is on
10In(Cmode) All T<0.1s  trip Cool Auxiliary switch closed, power is on
10(Dmode) All t>=0.1s  Don't trip Cool Auxiliary switch closed, power is on
14In(Dmode) All T<0.1s trip Cool Auxiliary switch closed, power is on

Detailed Photos

 

CE CB Approved 6ka MCB Circuit Breaker with Overload Protection ManufacturerCE CB Approved 6ka MCB Circuit Breaker with Overload Protection ManufacturerCE CB Approved 6ka MCB Circuit Breaker with Overload Protection ManufacturerCE CB Approved 6ka MCB Circuit Breaker with Overload Protection ManufacturerCE CB Approved 6ka MCB Circuit Breaker with Overload Protection ManufacturerCE CB Approved 6ka MCB Circuit Breaker with Overload Protection ManufacturerCE CB Approved 6ka MCB Circuit Breaker with Overload Protection ManufacturerCE CB Approved 6ka MCB Circuit Breaker with Overload Protection ManufacturerCE CB Approved 6ka MCB Circuit Breaker with Overload Protection Manufacturer