| Rated voltage(V) | Poles | Rated current (A) | Rated short circuit breaking capacity | |
| Test breaking capacity(KA) | Power factor | |||
| 230 | 1 | 6,10,16,20,25, 32,40,50,63 |
6 | 0.75 |
| 400 | 2,3,4 | 6 | ||
| Test current(A) | Rated current(A) | Requested time | Result | Start station | Remark |
| 1.13In | all | t>=1h | Don't trip | Cool | |
| 1.45In | All | T<1h | trip | heat | Current ascends the requested value stably in 5s |
| 2.55In | In<=32A | 1s<t<60s | trip | Cool | Auxiliary switch closed, power is on |
| 2.55In | In>32A | 1s<t<120s | trip | Cool | Auxiliary switch closed, power is on |
| 3In(Bmode) | All | t>=0.1s | Don't trip | Cool | Auxiliary switch closed, power is on |
| 5In(Bmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |
| 5In(Cmode) | All | t>=0.1s | Don't trip | Cool | Auxiliary switch closed, power is on |
| 10In(Cmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |
| 10(Dmode) | All | t>=0.1s | Don't trip | Cool | Auxiliary switch closed, power is on |
| 14In(Dmode) | All | T<0.1s | trip | Cool | Auxiliary switch closed, power is on |