Certification: | ISO9001, CCC |
---|---|
Protection: | Shock Resistance |
Installation: | Hanging |
Housing: | Thermoplastic Materials,UL94-0 |
Product Code: | Gns2 |
Standard: | IEC61643.1 |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Product Code | GNS2 |
Standard | IEC61643.1 / GB18802.1/ 1 Grade (T1) |
Rated Current (Maximum continuous operating voltage) Uc |
275V/385V |
Lightning impulse current (10/350 s)limp |
25KA |
Voltage protection level (Up to) |
<2.5KA |
Uc Time Power Frequency Continuous Current Breaking Capacity (L-M)In |
25KA mm |
Freewheeling suppression |
32A fuse does not jump when expected to continue to flow to 25KAMM |
response time |
<100ns |
Maximum reserve fuse (L) |
315AgL/gG |
Maximum reserve fuse (L-Lp) |
125AgL/gG |
Tolerance to Short Circuit for Maximum Backup Fuse |
25KA mm |
Range of Working Temperature | -40ºC...+80ºC |
Minimum Section Area of Installed Wire |
25mm2 stranded flexible Copper Wire |
Maximum Section Area of Installed Wire(L1,L2,L3N, PE) |
50mm2 stranded wire /35mm soft wire |
Installation | 35mmDIN rail, comply with EN50022 |
Shell Material | Red or white Thermoplastic materials,UL94-0 |
Protection Degree | IP20 |
Suppliers with verified business licenses